Micro-Ohmmeter and Ductor Testing Equipment for Hire

Megavar HV test equipment for hire. Specialist fleet of calibrated instruments for substation commissioning and maintenance across Australia.

Introduction

Megavar supplies micro-ohmmeters and ductor testers for hire across Australia, supporting contact resistance measurement on circuit breakers and switchgear, joint and connection resistance on busbars and conductors, and weld and bond integrity testing. The hire fleet covers the Megger DLRO low-resistance ohmmeter range across portable handheld units and high-current bench and field sets, from the everyday 10 A instrument through to high-current sets for the most demanding contact resistance work. The same instruments are used by Megavar commissioning engineers on substation and renewable energy projects every week.

A ductor test, the long-standing field name for a low-resistance measurement, answers one question that ordinary multimeters cannot: what is the true resistance of a current-carrying joint, contact, or connection, measured in micro-ohms. A loose or corroded busbar joint, a worn circuit breaker contact, or a poorly made cable lug presents a resistance of only tens or hundreds of micro-ohms, but at full load current that small resistance dissipates real heat, and heat is what eventually fails the connection. Measuring it reliably requires a four-terminal Kelvin measurement that eliminates the resistance of the test leads themselves, and a test current high enough to break through the surface films that would otherwise give a falsely high reading.

The Megavar micro-ohmmeter hire fleet is built on the Megger DLRO range, the established low-resistance ohmmeter family across Australian utilities and contractors. The fleet spans test currents from the portable 10 A handheld instrument, suitable for the bulk of contact and joint resistance work, up to high-current sets that drive the larger test currents some contact resistance specifications and high-current busbar joints require. Every instrument uses a four-terminal Kelvin measurement to eliminate lead resistance, and the higher-current units apply a forward and reverse current technique to cancel out standing thermal EMFs at the contact. Results store on the instrument and download for trend comparison against previous measurements on the same connection. Hire from our offices in Hobart, Launceston, Adelaide and Newcastle, with delivery Australia-wide and engineer-led support from a team that performs contact resistance testing as a regular part of substation commissioning and switchgear maintenance scopes.

Micro-ohmmeter and ductor testing applications

Circuit breaker contact resistance

Contact resistance across circuit breaker main contacts is a core commissioning and maintenance measurement. A rising contact resistance indicates contact wear, contamination, or mechanism misalignment, all of which lead to overheating under load. The measurement is taken across the closed contacts with a high test current, and compared against the manufacturer acceptance figure and against previous results on the same breaker.

Busbar, joint, and connection resistance

Bolted busbar joints, conductor connections, and cable lugs are measured to confirm the joint resistance is within specification and consistent across like joints. An outlier joint is the early warning of a connection that will overheat in service. High-current sets are used where the joint carries high current and the specification calls for a representative test current.

Weld, bond, and earth connection integrity

Low-resistance measurement confirms the integrity of welds, equipment bonds, and earth grid connections, distinguishing a sound bond from one that is mechanically tight but electrically poor. This is routine on substation steelwork, earth grid commissioning, and equipment earthing verification.

Commissioning verification on substation and renewable plant

Contact and joint resistance verification is a normal hold point in substation, solar farm, wind farm, and BESS commissioning. Megavar engineers perform these measurements as a regular part of commissioning scopes, which is why the hire fleet is maintained to commissioning standard.

When to Hire vs Buy

Hire from Megavar when...

  • You need a high-current ductor set for a single commissioning or maintenance campaign
  • Capital is constrained or the project rate does not justify outright purchase
  • Calibration and freight on owned equipment would exceed hire cost over the project life
  • You need engineer-led test set-up and result interpretation rather than the equipment alone
  • You need to scale several instruments in parallel during a multi-bay switchgear commissioning

Consider purchasing when...

  • Your team performs contact resistance testing on more than 60 days per year
  • You have in-house engineers competent on four-terminal high-current measurement
  • You can amortise the unit over its service life
  • Your asset programme commits to a multi-year contact resistance trend baseline
  • You require permanent on-call availability that hire cannot guarantee

Micro-Ohmmeter and Ductor Testing Equipment
Available for Hire

Megger

Megger DLRO 10A Micro-Ohmmeter

The DLRO 10A is a high-precision digital low resistance ohmmeter designed to measure very low resistance values with exceptional accuracy and repeatab…

Megger DLRO 100EB Micro-Ohmmeter

The Megger DLRO 100EB is a rugged, portable 100 A digital low-resistance ohmmeter engineered for high-accuracy micro-ohm measurements in high-voltage …

Megger DLRO 600A Micro-Ohmmeter

The DLRO 600A is a high‑current micro‑ohmmeter engineered for measuring extremely low resistances under real high‑current conditions. With test curren…

Megger MOM3 Handheld Micro-Ohmmeter

The 300 A Handheld Micro-ohmmeter is a powerful, portable instrument designed to measure very low resistances—typically in micro-ohms—with high accura…

Calibration

All Megavar test equipment is maintained under a documented calibration programme. Instruments are calibrated either by external calibration laboratories or in-house against reference standards that are themselves laboratory-calibrated, with measurement traceable to Australian national measurement standards held by the National Measurement Institute. A current calibration certificate is available on request. If your project requires a specific calibration interval, test standard, or documentation for a client submission, tell us at enquiry on 1300 730 499 and we will confirm what applies before you commit.

Get a quote for Micro-Ohmmeter and Ductor testing equipment hire

Australia-wide delivery, current calibration, engineer-led support. Most enquiries quoted same business day.

Talk to our engineers about your project requirements.

rentals@megavar.com.au

Frequently Asked Questions
for Micro-Ohmmeter and Ductor Testing Equipment

What is ductor testing?

Ductor testing is the field name for a low-resistance measurement, taken with a micro-ohmmeter, that measures the true resistance of a current-carrying joint, contact, or connection in micro-ohms. The name comes from the original Ductor instrument, and the term is still used across the industry for any contact or joint resistance test. It is used to confirm circuit breaker contacts, busbar joints, cable connections, and bonds are sound, because a high-resistance connection overheats under load and eventually fails.

A micro-ohmmeter measures very low resistance, in the micro-ohm and milli-ohm range, far below what a multimeter can resolve accurately. It uses a four-terminal Kelvin measurement that injects a known current through two terminals and measures the voltage drop across two separate terminals, which eliminates the resistance of the test leads and the contact resistance at the probes. A multimeter uses a two-terminal measurement where lead and contact resistance swamp the tiny resistance being measured, so it cannot give a meaningful contact or joint resistance reading.

Contact resistance testing measures the resistance across a closed electrical contact, most commonly a circuit breaker main contact, using a micro-ohmmeter at a defined test current. A rising contact resistance over successive tests indicates contact wear, contamination, or mechanism misalignment. The result is compared against the manufacturer acceptance figure and against previous measurements on the same contact, which is the basis of condition-based switchgear maintenance.

At the micro-ohm level, the resistance of the test leads and the contact resistance where the probes touch the connection are far larger than the resistance being measured, so a two-wire measurement is meaningless. A four-wire Kelvin measurement injects current through one pair of leads and measures voltage through a separate pair, so the lead and probe-contact resistance carry no measurement current and do not affect the result. Every instrument in the Megavar fleet uses a four-terminal Kelvin measurement.

The required test current depends on the acceptance specification for the asset. Many circuit breaker and switchgear specifications call for a test current of 100 A or higher so the measurement is representative of the contact under load and breaks through any surface films, while routine joint and connection work is often satisfied by a 10 A instrument. The Megavar fleet spans 10 A, 100 A, 300 A, and 600 A so the test current can be matched to the specification. If you are unsure, our engineers can advise against the relevant standard.

Standing thermal EMFs at the junction of dissimilar metals in a connection can add a small DC voltage that biases a low-resistance measurement. The forward-reverse current technique takes a measurement with the current flowing one way, then again with it reversed, and averages the two, which cancels out the standing EMF and gives a true resistance. The higher-current instruments in the Megavar fleet apply this automatically.

Yes. Low-resistance measurement confirms the integrity of welds, equipment bonds, and earth grid connections, distinguishing a connection that is mechanically tight but electrically poor from a sound one. This is routine on substation steelwork and earth grid commissioning. Note that earth grid resistance to remote earth is a separate measurement requiring an earth resistance tester, not a micro-ohmmeter; the micro-ohmmeter verifies the connections within the grid.

Yes. Megavar performs contact and joint resistance testing using the equipment in this rental fleet as a regular part of substation commissioning and switchgear maintenance, including test set-up, on-site execution, and result interpretation against manufacturer acceptance figures. If your project requires a turnkey survey rather than equipment hire alone, contact us with the asset type, the acceptance specification, and the test window, and we will quote a full scope.

Why Hire from Megavar

Megavar is a specialist HV testing and commissioning firm with offices in Hobart, Launceston, Adelaide and Newcastle. We perform contact and joint resistance testing as a regular part of substation commissioning and switchgear maintenance work for ElectraNet, TasNetworks, Downer, Acciona, Zinfra/Jemena, and renewable energy developers across Australia. The hire fleet exists because we built it for our own commissioning teams first, and we maintain it to the standard those teams require.

When you hire micro-ohmmeter and ductor testing equipment from Megavar you receive: full current calibration with traceable certificates, the complete current and potential lead set, a configuration tailored to your scope, and engineer-led pre-hire briefings on four-terminal connection technique and result interpretation. Our engineers can advise on the right test current for your acceptance specification, recommend the right instrument class for your scope, and help interpret the results against manufacturer acceptance figures. Where the project demands a turnkey contact resistance survey rather than equipment hire alone, we can quote on the full service. Hire periods are flexible from a single-day commissioning check through to multi-month maintenance campaigns. Delivery is Australia-wide. Call 1300 730 499 or email rentals@megavar.com.au.

Enquire about Micro-Ohmmeter and Ductor Testing Hire

Tell us about your project and we will get back to you within 24 hours with availability and a quote.

Or call us directly on 1300 730 499

Megavar Technician Conducting High Voltage (HV) Testing and Commissioning in an Outdoor Substation

Explore Our Services

Power system studies: load flow, short circuit, protection coordination, harmonic analysis, arc flash, and earthing studies. Supporting HV design, compliance, and grid connections across Australia.

Solar farm HV maintenance and testing: transformer diagnostics, switchgear testing, protection relay verification, thermography, and DGA monitoring for solar farms across Australia.

Circuit breaker testing across Australia: timing analysis, contact and dynamic resistance, insulation and SF6/vacuum integrity testing on HV and MV breakers, fully reported.

Trusted by top enterprises for exceptional results

AusNet logo - Megavar client
ABB logo - Megavar client
ElectraNet logo - Megavar client
Fluence logo - Megavar client
RJE Global logo - Megavar client
NYRStar logo - Megavar client
Schneider Electric logo - Megavar client
Acciona logo - Megavar client
RBD Electrical logo - Megavar client
Ventia logo - Megavar client
Grange logo - Megavar client
Alcoa logo - Megavar client
Zinfra logo - Megavar client
Bison Energy Company logo - Megavar client
Hydro Tasmania logo - Megavar client
TasNetworks logo - Megavar client
Vestas logo - Megavar client
Goldwind logo - Megavar client
Downer logo - Megavar client
ENERVEN logo - Megavar client
Genus logo - Megavar client

Explore the latest insights