Equipment hire
CT Testing Equipment for Hire
Day rates, 1 to 7 days, ex GST:
- Omicron CPX 200 for Hire Multifunctional Test Set$600
- Omicron HVX10 for Hire 10 kV High-Voltage Source$420
- Omicron CPC 100 Multi-Function Primary Test Set$550
- Omicron CT Analyser Set$335
Every rate band is on the instrument page. Minimum hire one day.
Current transformer (CT) testing is one of the most volume-intensive disciplines on every substation commissioning and protection scheme project. Megavar supplies the complete fleet of CT testing equipment for hire across Australia: Omicron CT Analyser sets and CT SB2 switch boxes for fast secondary-injection testing, CPC 100, CPX 200 and HVX10 primary injection sets for end-to-end ratio and polarity verification, the CP TD1 accessory for tan delta on HV CT bushings, and Megger MIT 5 kV and MIT 10 kV insulation resistance testers. All hires are backed by engineers who commission CTs to IEC 61869 and IEEE C57.13 every month.
Rates per day, ex GST
CT Testing Equipment Available for Hire
Each instrument is supplied with its manuals. If one plays up, call us and we will arrange a fix or a replacement. No computer is supplied: where an instrument needs software, install it on your own computer.
Omicron
Calibration
All Megavar test equipment is maintained under a documented calibration programme. Instruments are calibrated either by external calibration laboratories or in-house against reference standards that are themselves laboratory-calibrated, with measurement traceable to Australian national measurement standards held by the National Measurement Institute. A current calibration certificate is available on request. If your project requires a specific calibration interval, test standard, or documentation for a client submission, tell us at enquiry on 1300 730 499 and we will confirm what applies before you commit.
Megger
Get a quote for CT testing equipment hire
Secondary-injection CT analysers, primary injection sets, tan delta and IR testers. Current calibration and Australia-wide delivery.
Tell us what you need and when, and we will come back with availability and pricing.
About ct testing equipment hire
CT Testing Equipment hire, in more detail
Introduction
CT testing verifies that a current transformer will deliver an accurate, in-phase secondary current to its connected protection relays and metering circuits across the full operating range of the asset. Modern testing covers ratio accuracy, phase displacement, polarity, the excitation (saturation) curve, the knee point voltage, winding resistance, burden, and insulation resistance. For protection CTs the test programme also confirms accuracy class limits including composite error, instrument security factor (FS) and accuracy limit factor (ALF). For metering CTs the programme confirms compliance with revenue accuracy class requirements at the specified rated burden.
The dominant test method on Australian projects is low-energy secondary injection using the Omicron CT Analyser, which captures the complete CT performance characteristic in under a minute per CT and applies an automatic pass/fail assessment against the selected standard. Primary injection using a CPC 100 or CPX 200 is used where the project specification calls for end-to-end primary-side verification, where the CT design or installation does not permit secondary-side testing, or where critical protection schemes such as transformer differential, busbar protection and line differential require an independent primary check on top of the CT Analyser results. The two methods are complementary, not competing.
CT testing in Australia is governed by IEC 61869-1 (general requirements for instrument transformers) and IEC 61869-2 (current transformers), with IEC 60044-1 still referenced on legacy assets. IEEE C57.13 applies where the project specification calls for IEEE compliance, and AEMO metering CT requirements apply to revenue metering installations under the National Electricity Rules. Megavar’s commissioning engineers test CTs against all four standards from offices in Hobart, Launceston, Adelaide and Newcastle, with delivery Australia-wide.
CT Testing Applications and Standards
CT testing is performed across the full project lifecycle, from factory acceptance through commissioning to periodic asset management. The right test programme depends on what the CT is being installed for, what the project specification calls for, and what evidence the asset owner needs at handover.
Substation commissioning
Greenfield and brownfield substation commissioning is the highest-volume CT testing scope on Megavar projects. Every CT in every bay is tested for ratio, polarity, excitation, winding resistance and burden against the nameplate, with the results compiled into the commissioning records that are handed back to the asset owner at energisation. The CT Analyser with the CT SB2 switch box is the standard tool for this work because it tests all secondary taps in a single automated run.
Revenue metering CT compliance
Revenue metering CTs must be verified against the accuracy class declared on the nameplate (Class 0.2, 0.2S, 0.5 or 0.5S) at rated burden. AEMO metering rules under the National Electricity Rules set out the test and verification regime for Type 1 to Type 7 metering installations, and the CT Analyser provides the documented evidence required for compliance. Where the metering installation has been disturbed, the test must be repeated and the result lodged before metering can be re-energised.
Protection scheme verification
Critical protection schemes including transformer differential, busbar protection, line differential and high-impedance restricted earth fault rely on accurate, in-phase CT secondary currents from multiple CTs on the same protected zone. CT verification for these schemes typically combines a CT Analyser pass against the protection class (5P, 10P, PX, TPX, TPY or TPZ) with a primary injection check using the CPC 100 to confirm correct wiring, polarity and end-to-end ratio. Megavar performs this combination of tests on every major protection commissioning.
CT excitation and knee point characterisation
The excitation curve plots the secondary voltage required to produce a given exciting current in the CT secondary. The curve identifies the knee point, above which the CT begins to saturate. Knee point voltage and the maximum exciting current at the knee point are critical inputs to differential and high-impedance scheme calculations, and to verification of CT adequacy under fault conditions. The CT Analyser captures the full excitation curve in seconds and reports the knee point automatically.
Periodic asset management and post-fault investigation
Asset owners increasingly include CT verification in their cyclic maintenance programmes, particularly for transmission-class CTs and HV bushing CTs where in-service degradation is a real risk. Tan delta measurement on the HV CT insulation using the CP TD1 accessory paired with a CPC 100 detects ageing and contamination of the bushing insulation system. After a major fault on a protected zone, CT testing forms part of the standard post-fault investigation to confirm that the CTs themselves remained within their declared performance class during and after the fault.
Secondary versus Primary Injection
CT testing splits between two test methodologies, and a complete project usually uses both. The right method for a given test depends on what the project specification calls for and what level of end-to-end verification is required.
Secondary injection (CT Analyser method)
Secondary injection uses a low-voltage, low-energy signal applied to the CT secondary winding, with the CT Analyser deriving the complete equivalent-circuit model of the transformer from the measured response. From this model, ratio, phase displacement, excitation curve, knee point, polarity, burden and winding resistance are all calculated and assessed against the selected standard. Test voltage is typically below 120 V which makes the method significantly safer than legacy high-current primary injection, the test runs in under a minute per CT, and the demagnetisation cycle at the end of the test leaves the CT ready for service. This is the dominant method for substation commissioning in Australia and is accepted by all major asset owners as the primary CT acceptance test.
Primary injection (CPC 100 method)
Primary injection applies a known current through the CT primary, typically the busbar or primary conductor, and measures the resulting secondary current at the relay terminals. This verifies the entire CT, wiring, terminal connections and relay path in one shot, which is the strongest possible end-to-end check on protection scheme integrity. Primary injection is mandatory under some asset-owner specifications, is the established method for verifying critical schemes such as transformer differential and busbar protection, and is the test of last resort where secondary-side access is restricted or where the CT design does not support secondary injection. The Omicron CPC 100 is Megavar’s standard primary injection toolkit, with the Omicron CPX 200 (and its HVX10 high-voltage attachment) available where a second multifunction set or a higher test voltage is needed.
How they fit together
Most major commissioning projects use both methods. The CT Analyser handles the bulk volume of CT acceptance testing, providing a fast, documented pass against the nameplate class for every CT. The CPC 100 then handles end-to-end primary injection on critical protection schemes, on revenue metering installations where the project specification mandates it, and on any CT where the CT Analyser result is ambiguous or contested. Megavar’s engineers run this combined workflow as routine.
When to Hire vs Buy
CT testing equipment is a sensible candidate for hire on most project profiles. The Omicron CT Analyser and CPC 100 are class-leading instruments and the cost of ownership reflects that. Hire makes economic sense for project-driven workloads; ownership only makes sense for organisations with year-round high-volume CT testing demand.
Hire from Megavar when...
- You need a CT Analyser for a project window from a single day to several months
- You need a primary injection set for a one-off scheme commissioning
- Your team handles CT testing on commissioning projects but not as a year-round activity
- You want results interpreted by engineers who test CTs every month
- The project specification calls for both secondary and primary injection across multiple bays
- You need the CT SB2 switch box for a multi-bay substation but only on this project
Consider purchasing when...
- Your team performs CT testing as a year-round routine activity
- You commission more than 200 CTs per year across multiple sites
- You have qualified protection engineers in-house with current CT testing competency
- You can commit to ongoing manufacturer training and software updates
- Your asset register justifies a multi-year programme of CT condition monitoring
- Your organisation can absorb 3 to 5 year obsolescence on the measurement platform
Why Hire from Megavar
CT testing is one of the highest-volume disciplines in HV commissioning and one of the most consequential. A wrongly tested CT produces a false-positive acceptance record that the asset owner relies on for years afterwards, and the protection scheme it feeds may never function as intended until a real fault occurs. Megavar’s commissioning engineers test CTs to IEC 61869 every month on transmission and distribution projects, including BESS step-up CTs, transmission line CTs, transformer bushing CTs, distribution switchgear CTs and revenue metering installations.
When you hire CT testing equipment from Megavar you receive: current calibration with traceable certificates, the matched accessories and software licences for the asset class you are testing, and the manufacturer's manuals. Where the project requires CT testing done end-to-end rather than equipment alone, we can quote a turnkey commissioning service with our protection engineers operating the equipment, running the test programme and producing the commissioning records. This is the most common arrangement on substation commissioning, scheme verification, revenue metering compliance and post-fault investigation.
Hire periods are flexible from single-day commissioning checks through to multi-month project rentals. Delivery is Australia-wide. Call 1300 730 499 or email rentals@megavar.com.au.
Before you get to site
CT Testing: A Field Guide to Ratio, Polarity, Excitation and Burden Tests on Current Transformers
A Megavar field guide to the test: what it proves, how it is set up and how to read the result.
Capability statement
Test Equipment Rental
The HV test equipment hire fleet by category, with calibration, hire terms and delivery.
How the hire works
Hire terms in brief
After you enquire
We confirm availability, rates and freight in a written quote, valid for the period it states (usually 14 days). An enquiry or quote does not reserve equipment: the hire is booked when your purchase order, signed quote or email acceptance reaches us.
Hire period
Our carrier: up to 72 hours of transit each way is not charged as hire. Hire starts at delivery or 72 hours after dispatch, whichever is earlier, and ends at handover to our carrier or 72 hours before the equipment arrives back, whichever is later. Delay caused by us or our carrier is not charged. For example, dispatched Monday 10am and delivered Wednesday 2pm: hire starts Wednesday 2pm. Routes that normally take longer than 72 hours are marked on the quote. Your own freight: hire runs from handover to your carrier at our office until the equipment arrives back at our office. Collect in person: from collection to return.
Extensions and early return
Contact us before the return deadline to extend; your quoted rates stay fixed and extended hire is invoiced every 7 days. Return early and you pay only for the days used, at the rate band for the days actually hired.
Delivery and returns
Freight for each leg, the handling fee and any express dispatch are on the quote, before you accept. Returns go to the dispatching office named on the quote, by carrier or in person, never by post.
Counter times
Returned to our counter before 9am on a business day counts as the previous day. Collected after 4pm on a business day, hire starts the next day. Weekends and public holidays count as hire days.
Calibration and checks
Supplied in working order with listed accessories, leads and manuals. Each measuring instrument is calibrated, and its current NATA-traceable calibration certificate is available on request. If calibration falls due during your hire, we tell you before dispatch.
Cancelling or moving a booking
Cancel 5 or more business days before dispatch or collection and nothing is charged. With 2 to 4 business days’ notice, the charge is the greater of one day’s hire and 5% of the booked hire; with less notice, the greater of one day’s hire and 10%. You can ask once to move the start by up to 30 days, with at least 2 business days’ notice.
Loss, damage and insurance
The equipment is your responsibility, other than fair wear and tear, from the start of hire until it is back with us, including in transit, up to the replacement value cap shown on the quote for each item. No damage waiver is offered. We recommend you insure the equipment for its replacement value.
Payment and bond
Account customers pay each invoice within 14 days. Without a credit account, or paying by card, you pay the booked hire, freight, handling fee and any bond before dispatch. A bond applies only where the quote states one, and is refunded after return and inspection, less anything owed.
Summary of our Terms and Conditions: Test Equipment Hire. Full hire terms
Enquire about CT Testing Equipment Hire
Check availability
Send your hire dates and delivery location and we will confirm availability and lead time by the end of the next business day.
Or call us directly on 1300 730 499
Need help with your rental?
1300 730 499 We’re available Monday to Friday, 8:30 am to 5:00 pm. Urgent hire: call rather than send the form. rentals@megavar.com.auFAQ
Frequently Asked Questions for CT Testing Equipment
What does a CT Analyser test?
What is the difference between secondary injection and primary injection CT testing?
What standards apply to CT testing in Australia?
Can the Omicron CT Analyser test multi-tap CTs?
Do I need primary injection for revenue metering CT compliance?
What is a CT excitation curve and why does it matter?
How does the CT Analyser handle protection versus metering CT classes?
Can Megavar provide CT testing as a turnkey service rather than just hire?
Do you deliver CT test equipment Australia-wide?
Explore Rental Categories
Explore Our Services
Trusted by top enterprises for exceptional results



Testing guides
Related testing guides
CT Testing: A Field Guide to Ratio, Polarity, Excitation and Burden Tests on Current Transformers
CT testing proves that a current transformer has the ratio and polarity on its nameplate, a healthy magnetic core and sound secondary insulation. This guide explains…
Secondary Isolation: CT Shorting Links, Test Blocks and Trip Isolation for Protection Testing
Secondary isolation separates the protection, control and metering circuits under test from the circuits that stay in service. This guide sets out the principles: CT shorting…
Protection Relay Testing: Secondary Injection, Test Intervals and the Standards That Apply
Protection relay testing proves that the relays guarding a substation, feeder or generator will trip when they should and stay stable when they should not. This…
Minimum hire one day View instruments