CT Testing Equipment for Hire

Current transformer (CT) testing is one of the most volume-intensive disciplines on every substation commissioning and protection scheme project. Megavar supplies the complete fleet of CT testing equipment for hire across Australia: Omicron CT Analyser sets and CT SB2 switch boxes for fast secondary-injection testing, CPC 100, CPX 200 and HVX10 primary injection sets for end-to-end ratio and polarity verification, the CP TD1 accessory for tan delta on HV CT bushings, and Megger MIT 5 kV and MIT 10 kV insulation resistance testers. All hires are backed by engineers who commission CTs to IEC 61869 and IEEE C57.13 every month.

Megavar HV test equipment for hire. Specialist fleet of calibrated instruments for substation commissioning and maintenance across Australia.

Introduction

CT testing verifies that a current transformer will deliver an accurate, in-phase secondary current to its connected protection relays and metering circuits across the full operating range of the asset. Modern testing covers ratio accuracy, phase displacement, polarity, the excitation (saturation) curve, the knee point voltage, winding resistance, burden, and insulation resistance. For protection CTs the test programme also confirms accuracy class limits including composite error, instrument security factor (FS) and accuracy limit factor (ALF). For metering CTs the programme confirms compliance with revenue accuracy class requirements at the specified rated burden.

 

The dominant test method on Australian projects is low-energy secondary injection using the Omicron CT Analyser, which captures the complete CT performance characteristic in under a minute per CT and applies an automatic pass/fail assessment against the selected standard. Primary injection using a CPC 100 or CPX 200 is used where the project specification calls for end-to-end primary-side verification, where the CT design or installation does not permit secondary-side testing, or where critical protection schemes such as transformer differential, busbar protection and line differential require an independent primary check on top of the CT Analyser results. The two methods are complementary, not competing.

 

CT testing in Australia is governed by IEC 61869-1 (general requirements for instrument transformers) and IEC 61869-2 (current transformers), with IEC 60044-1 still referenced on legacy assets. IEEE C57.13 applies where the project specification calls for IEEE compliance, and AEMO metering CT requirements apply to revenue metering installations under the National Electricity Rules. Megavar’s commissioning engineers test CTs against all four standards from offices in Hobart, Launceston, Adelaide and Newcastle, with delivery Australia-wide.

CT Testing Applications and Standards

CT testing is performed across the full project lifecycle, from factory acceptance through commissioning to periodic asset management. The right test programme depends on what the CT is being installed for, what the project specification calls for, and what evidence the asset owner needs at handover.

 

Substation commissioning

 

Greenfield and brownfield substation commissioning is the highest-volume CT testing scope on Megavar projects. Every CT in every bay is tested for ratio, polarity, excitation, winding resistance and burden against the nameplate, with the results compiled into the commissioning records that are handed back to the asset owner at energisation. The CT Analyser with the CT SB2 switch box is the standard tool for this work because it tests all secondary taps in a single automated run.

 

Revenue metering CT compliance

 

Revenue metering CTs must be verified against the accuracy class declared on the nameplate (Class 0.2, 0.2S, 0.5 or 0.5S) at rated burden. AEMO metering rules under the National Electricity Rules set out the test and verification regime for Type 1 to Type 7 metering installations, and the CT Analyser provides the documented evidence required for compliance. Where the metering installation has been disturbed, the test must be repeated and the result lodged before metering can be re-energised.

 

Protection scheme verification

 

Critical protection schemes including transformer differential, busbar protection, line differential and high-impedance restricted earth fault rely on accurate, in-phase CT secondary currents from multiple CTs on the same protected zone. CT verification for these schemes typically combines a CT Analyser pass against the protection class (5P, 10P, PX, TPX, TPY or TPZ) with a primary injection check using the CPC 100 to confirm correct wiring, polarity and end-to-end ratio. Megavar performs this combination of tests on every major protection commissioning.

 

CT excitation and knee point characterisation

 

The excitation curve plots the secondary voltage required to produce a given exciting current in the CT secondary. The curve identifies the knee point, above which the CT begins to saturate. Knee point voltage and the maximum exciting current at the knee point are critical inputs to differential and high-impedance scheme calculations, and to verification of CT adequacy under fault conditions. The CT Analyser captures the full excitation curve in seconds and reports the knee point automatically.

 

Periodic asset management and post-fault investigation

 

Asset owners increasingly include CT verification in their cyclic maintenance programmes, particularly for transmission-class CTs and HV bushing CTs where in-service degradation is a real risk. Tan delta measurement on the HV CT insulation using the CP TD1 accessory paired with a CPC 100 detects ageing and contamination of the bushing insulation system. After a major fault on a protected zone, CT testing forms part of the standard post-fault investigation to confirm that the CTs themselves remained within their declared performance class during and after the fault.

Secondary versus Primary Injection

CT testing splits between two test methodologies, and a complete project usually uses both. The right method for a given test depends on what the project specification calls for and what level of end-to-end verification is required.

 

Secondary injection (CT Analyser method)

 

Secondary injection uses a low-voltage, low-energy signal applied to the CT secondary winding, with the CT Analyser deriving the complete equivalent-circuit model of the transformer from the measured response. From this model, ratio, phase displacement, excitation curve, knee point, polarity, burden and winding resistance are all calculated and assessed against the selected standard. Test voltage is typically below 120 V which makes the method significantly safer than legacy high-current primary injection, the test runs in under a minute per CT, and the demagnetisation cycle at the end of the test leaves the CT ready for service. This is the dominant method for substation commissioning in Australia and is accepted by all major asset owners as the primary CT acceptance test.

 

Primary injection (CPC 100 method)

 

Primary injection applies a known current through the CT primary, typically the busbar or primary conductor, and measures the resulting secondary current at the relay terminals. This verifies the entire CT, wiring, terminal connections and relay path in one shot, which is the strongest possible end-to-end check on protection scheme integrity. Primary injection is mandatory under some asset-owner specifications, is the established method for verifying critical schemes such as transformer differential and busbar protection, and is the test of last resort where secondary-side access is restricted or where the CT design does not support secondary injection. The Omicron CPC 100, with the CPX 200 booster amplifier and HVX10 voltage source where higher current or voltage is needed, is Megavar’s standard primary injection toolkit.

 

How they fit together

 

Most major commissioning projects use both methods. The CT Analyser handles the bulk volume of CT acceptance testing, providing a fast, documented pass against the nameplate class for every CT. The CPC 100 then handles end-to-end primary injection on critical protection schemes, on revenue metering installations where the project specification mandates it, and on any CT where the CT Analyser result is ambiguous or contested. Megavar’s engineers run this combined workflow as routine and can advise on the right balance for your scope.

When to Hire vs Buy

CT testing equipment is a sensible candidate for hire on most project profiles. The Omicron CT Analyser and CPC 100 are class-leading instruments and the cost of ownership reflects that. Hire makes economic sense for project-driven workloads; ownership only makes sense for organisations with year-round high-volume CT testing demand.

Hire from Megavar when...

  • You need a CT Analyser for a project window from a single day to several months
  • You need a primary injection set for a one-off scheme commissioning
  • Your team handles CT testing on commissioning projects but not as a year-round activity
  • You want results interpreted by engineers who test CTs every month
  • The project specification calls for both secondary and primary injection across multiple bays
  • You need the CT SB2 switch box for a multi-bay substation but only on this project

Consider purchasing when...

  • Your team performs CT testing as a year-round routine activity
  • You commission more than 200 CTs per year across multiple sites
  • You have qualified protection engineers in-house with current CT testing competency
  • You can commit to ongoing manufacturer training and software updates
  • Your asset register justifies a multi-year programme of CT condition monitoring
  • Your organisation can absorb 3 to 5 year obsolescence on the measurement platform

CT Testing Equipment
Available for Hire

Omicron

Omicron CPX 200 for Hire Multifunctional Test Set

The Omicron CPX 200 is a next-generation multifunctional test set for commissioning, maintenance, and condition assessment of medium and high-voltage …

Omicron HVX10 for Hire 10 kV High-Voltage Source

The Omicron HVX10 is a compact 10 kV AC/DC high-voltage source that attaches to the CPX 200 multifunctional test set via Omicron’s Click-Snap-Lock mec…

Omicron CPC 100 Multi-Function Primary Test Set

The Omicron CPC 100 is a universal primary injection test system designed for high-precision testing of power transformers, CTs, VTs, circuit breakers…

Omicron CT Analyser Set

The CTA (Current Transformer Analyser) from Omicron is a dedicated testing system for verifying the performance and accuracy of current transformers (…

Omicron CT Analyser Switch Box (CTSB2)

The CT Analyser Switch Box Expansion is an optional accessory designed to streamline multi-ratio and multi-core current transformer (CT) testing using…

Omicron CP TD1 Tan Delta Accessory

The CP + TD1 is a powerful test accessory designed for use with the OMICRON CPC 100 to perform accurate tan delta (dissipation factor) and capacitance…

Megger MIT520 5kV Insulation Resistance Tester

The MIT 5kV Insulation Resistance Tester is a compact and reliable digital megohmmeter used for insulation testing of cables, motors, generators, swit…

Megger MIT1020 10kV Insulation Resistance Tester

The MIT 10kV Insulation Resistance Tester is a high-voltage digital megohmmeter designed for advanced insulation testing on critical electrical infras…

Pfisterer CONNEX Grounding and Current Testing Connector (Size 0)

The CONNEX socket is a separable bushing interface used widely on European-supplied transformers, switchgear, and instrument transformers. The Pfister…

Calibration

All Megavar test equipment is maintained under a documented calibration programme. Instruments are calibrated either by external calibration laboratories or in-house against reference standards that are themselves laboratory-calibrated, with measurement traceable to Australian national measurement standards held by the National Measurement Institute. A current calibration certificate is available on request. If your project requires a specific calibration interval, test standard, or documentation for a client submission, tell us at enquiry on 1300 730 499 and we will confirm what applies before you commit.

Megger

Get a quote for CT testing equipment hire

Secondary-injection CT analysers, primary injection sets, tan delta and IR testers. Engineer-led testing and Australia-wide delivery.

Talk to our engineers about your project requirements.

rentals@megavar.com.au

Frequently Asked Questions
for CT Testing Equipment

What does a CT Analyser test?
A CT Analyser tests every parameter required to verify a current transformer against its nameplate class and the applicable standard. The standard test sequence covers ratio accuracy at rated burden, phase displacement, polarity, the full excitation curve, knee point voltage, secondary winding resistance, burden, and insulation resistance on the secondary winding. For protection CTs it derives composite error, accuracy limit factor (ALF) and instrument security factor (FS). For metering CTs it confirms compliance with the declared accuracy class at rated burden. The Omicron CT Analyser performs the complete sequence in under a minute per CT and produces an automatic pass/fail report against IEC 61869, IEC 60044, IEEE C57.13 or AS 61869, whichever is selected.
Secondary injection applies a low-voltage signal to the CT secondary winding and derives the complete CT performance characteristic from the measured response. The CT Analyser is the standard tool, the test runs in under a minute per CT at safe voltages, and the result is a documented pass against the nameplate class. Primary injection applies a known current through the CT primary, typically the busbar or primary conductor, and measures the secondary current at the relay terminals. This verifies the entire CT plus wiring plus relay path end-to-end, which is the strongest possible check on protection scheme integrity. Most projects use both: secondary injection for the bulk of the CT acceptance volume, and primary injection on critical protection schemes, on revenue metering installations where the specification mandates it, and on any CT where the secondary-injection result is ambiguous.
The current reference standards are IEC 61869-1 (general requirements for instrument transformers) and IEC 61869-2 (specific requirements for current transformers). IEC 60044-1 is the legacy standard, replaced by IEC 61869-2 but still referenced on older Australian assets and on legacy project specifications. IEEE C57.13 applies where the project specification calls for IEEE compliance, and AS 61869 is the Australian adoption of the IEC standard. AEMO metering CT requirements under the National Electricity Rules apply to revenue metering installations and are stricter than the IEC accuracy class limits. Megavar’s commissioning engineers test CTs against all four standards and will configure the CT Analyser for whichever is specified.
Yes. Multi-tap CTs are tested by the CT Analyser tap by tap, with the result for each tap recorded against the corresponding nameplate ratio. On a single multi-tap CT the operator reconnects the test leads between taps. On multi-bay substations with many multi-tap CTs the CT SB2 switch box accessory automates this completely: the SB2 connects to all secondary taps in a single setup and the CT Analyser steps through them under software control without manual rewiring. The SB2 is the recommended configuration for any project with more than a handful of multi-tap CTs because it dramatically reduces reconnection time and eliminates connection errors.
It depends on the metering installation type and the asset owner specification. For most Type 1 to Type 7 metering installations under the AEMO metering rules, secondary-injection testing with a CT Analyser is accepted as the primary verification method, with the CT Analyser report providing the documented evidence required for compliance. On larger Type 1 metering installations and on installations where the asset owner specification calls for primary-side verification, an additional primary injection check using the CPC 100 is required. Megavar’s engineers run revenue metering CT compliance testing on both bases and can advise on the right approach for your installation.
The excitation curve plots the secondary voltage required to produce a given exciting current in the CT secondary winding. The curve identifies the knee point, above which the CT begins to saturate. Knee point voltage and the maximum exciting current at the knee point are critical inputs to differential, high-impedance and busbar protection scheme calculations, where CT saturation under fault conditions can cause maloperation. The CT Analyser captures the full excitation curve in seconds and reports the knee point automatically against the relevant standard. For PX and TPX class CTs the curve is the primary acceptance criterion.
The CT Analyser supports the full range of CT classes used in Australian practice: metering classes 0.2, 0.2S, 0.5, 0.5S, 1 and 3, and protection classes 5P, 10P, PX, TPX, TPY and TPZ. The operator selects the nameplate class in the test setup and the software applies the correct evaluation criteria automatically. For metering CTs the assessment focuses on ratio and phase displacement at rated burden against the class accuracy limits. For protection CTs the assessment covers composite error, accuracy limit factor and the excitation curve against the protection class limits. Combined metering-protection CTs with multiple secondary cores are tested core by core against each declared class.
Yes. Megavar provides full CT commissioning and verification services using the equipment in this rental fleet. The turnkey scope covers test plan development, on-site secondary and primary injection testing, results interpretation, exception management and a complete written commissioning record signed off by a qualified protection engineer. This is the most common arrangement for substation commissioning, critical scheme verification, revenue metering compliance and post-fault investigation. Contact us with the asset class, voltage level, CT count and project schedule and we will quote a complete scope
Yes. Megavar dispatches CT test equipment from offices in Hobart, Launceston, Adelaide and Newcastle. The CT Analyser, CT SB2 switch box, MIT 5 kV and MIT 10 kV all dispatch in handheld carry cases and can reach most centres overnight. The CPC 100, CPX 200 and HVX10 require dedicated freight arrangements. The CP TD1 tan delta accessory is dispatched as part of a CPC 100 bundle. Where the project requires the equipment operated by Megavar engineers, freight, set-up and operation are coordinated as a single mobilisation by our commissioning team.

Why Hire from Megavar

CT testing is one of the highest-volume disciplines in HV commissioning and one of the most consequential. A wrongly tested CT produces a false-positive acceptance record that the asset owner relies on for years afterwards, and the protection scheme it feeds may never function as intended until a real fault occurs. Megavar’s commissioning engineers test CTs to IEC 61869 every month on transmission and distribution projects, including BESS step-up CTs, transmission line CTs, transformer bushing CTs, distribution switchgear CTs and revenue metering installations.

 

When you hire CT testing equipment from Megavar you receive: current calibration with traceable certificates, the matched accessories and software licences for the asset class you are testing, and pre-hire engineer briefings on test set-up and acceptance criteria. Where the project requires CT testing done end-to-end rather than equipment alone, we can quote a turnkey commissioning service with our protection engineers operating the equipment, running the test programme and producing the commissioning records. This is the most common arrangement on substation commissioning, scheme verification, revenue metering compliance and post-fault investigation.

 

Hire periods are flexible from single-day commissioning checks through to multi-month project rentals. Delivery is Australia-wide. Call 1300 730 499 or email rentals@megavar.com.au.

Enquire about CT Testing Equipment Hire

Tell us about your project and we will get back to you within 24 hours with availability and a quote.

Or call us directly on 1300 730 499

Megavar Technician Conducting High Voltage (HV) Testing and Commissioning in an Outdoor Substation

Explore Our Services

HV testing and commissioning by Megavar's own engineers. Substations, transformers, cables, switchgear. 200+ instrument fleet, four offices nationwide.

SCADA engineering and integration for substations and renewable energy projects. RTU configuration, IEC 61850, DNP3, cybersecurity, and end-to-end commissioning across Australia.

Substation maintenance services: preventive, corrective, and condition-based maintenance for HV transformers, switchgear, protection, and SCADA across Australia. Omicron test equipment.

Trusted by top enterprises for exceptional results

AusNet logo - Megavar client
ABB logo - Megavar client
ElectraNet logo - Megavar client
Fluence logo - Megavar client
RJE Global logo - Megavar client
NYRStar logo - Megavar client
Schneider Electric logo - Megavar client
Acciona logo - Megavar client
RBD Electrical logo - Megavar client
Ventia logo - Megavar client
Grange logo - Megavar client
Alcoa logo - Megavar client
Zinfra logo - Megavar client
Bison Energy Company logo - Megavar client
Hydro Tasmania logo - Megavar client
TasNetworks logo - Megavar client
Vestas logo - Megavar client
Goldwind logo - Megavar client
Downer logo - Megavar client
ENERVEN logo - Megavar client
Genus logo - Megavar client

Explore the latest insights