Testing and commissioning services

Partial Discharge Testing Services Australia

Talk to an engineer: 1300 730 499 or service@megavar.com.au

Detect Insulation Defects Before They Become Failures


Partial discharge (PD) is a localised electrical discharge within HV insulation that does not fully bridge conductors. Individually small, PD is a symptom of insulation degradation that will progressively worsen to complete failure if undetected. Megavar provides online and offline PD testing for cables, switchgear, transformers, GIS, and rotating machines across Australia.

ISO 9001, 14001 and 45001 certifiedLicensed in every Australian stateTeams in Hobart, Launceston, Adelaide and Newcastle
Partial discharge testing on high voltage switchgear in Australian substation

Online PD Testing

Performed while equipment remains energised and in service – no outage required. We use TEV (transient earth voltage), HFCT (high-frequency current transformer), and UHF sensors to detect and locate PD in switchgear, cable terminations, joints, and transformer bushings under normal operating conditions.

Offline PD Testing

Equipment de-energised with external voltage source applied for more sensitive, calibrated measurement. Includes phase-resolved PD (PRPD) pattern analysis for defect classification using the Omicron MPD 600 partial discharge system, per IEC 60270.

Case study: locating PD sources on new 22 kV switchgear

Equipment We Test

  • HV cables and joints – XLPE and oil-filled cables 11–220 kV. Void defects, contamination, termination/joint issues.
  • Switchgear – AIS and GIS. Particle contamination, tracking, contact degradation.
  • Power transformers – Bushing defects, tap changer insulation, winding degradation.
  • Instrument transformers – Internal insulation defects that can cause catastrophic failure.
  • Rotating machines – Stator winding insulation for generators and HV motors.

Standards

Per IEC 60270, IEC 62478, CIGRE TB 728/861, and IEEE 400. Results interpreted by experienced engineers who classify severity, type, and likely defect location.

Take it to your team

Capability statement

High-Voltage Resonant Hipot Testing

AC withstand testing to 500 kV on Megavar-owned resonant test sets, with partial discharge measurement.

Capability statement

High-Voltage Testing, Commissioning and Maintenance Services

Primary plant testing, protection and SCADA commissioning, substation maintenance and the design capability behind them.

Clients

What our clients say

Megavar are industry leaders in HV commissioning services, offering high quality commissioning services. They are experts in high voltage commissioning services, and their work is always on time, on budget and to the highest quality.

Shaun ColtonEngineering Manager Substations & BESS, Downer Group

Megavar has repeatedly demonstrated their ability to quickly mobilise their highly skilled technicians to meet project demands and effectively develop solutions in a highly proficient and professional manner.
Megavar have been a pleasure to deal with, and we look forward to continuing to work closely on future projects for years to come.

Matt LawlessDirector – High Voltage Contracting

FAQ

Frequently Asked Questions Partial Discharge Testing Services Australia

What is partial discharge testing?

PD testing detects localised electrical discharges within HV insulation caused by voids, contamination, or damage. Early detection enables planned repairs before complete insulation failure, avoiding unplanned outages and catastrophic damage.

What is the difference between online and offline PD testing?

Online PD testing is done while equipment is energised – no outage needed. Uses sensors (TEV, HFCT, UHF) under normal conditions. Offline requires de-energisation and external voltage for more sensitive, calibrated measurements with PRPD pattern analysis.

Can PD testing be done without a shutdown?

Yes. Online PD testing requires no interruption to service – ideal for critical assets where outages are difficult to schedule.

What defects can PD testing detect?

Voids in solid insulation, surface contamination and tracking, loose particles in switchgear, degraded joints and terminations, bushing deterioration, and moisture ingress in oil-filled equipment.

Does Megavar provide PD testing nationally?

Yes. We deploy from offices in Tasmania, SA, NSW and Queensland to sites across all states and territories.

ISO Certified and Licensed in Every State

Megavar is certified to ISO 9001 (quality), ISO 14001 (environment) and ISO 45001 (safety), and holds electrical contractors licences in every Australian state.

Ready to commission your substation? Contact Megavar today on 1300 730 499 or visit our contact page to request a quote.

Contact Us

Request a quote

Tell us about the job

An engineer replies by the end of the next business day (Monday to Friday, 8:30 am to 5:00 pm). Scope still forming? Send what you have. Outage or urgent fault? Call to discuss the site, access window and mobilisation.

Scope status
Drag & Drop Files, Choose Files to Upload

* Required.

Megavar Pty Ltd (ABN 88 104 344 765) collects these details, and any file you attach, to prepare your quote, respond to your enquiry and keep a record of it, and to understand how enquiries reach us. If you do not provide them we may not be able to quote. We may share them with our IT, email and business system providers and, where relevant, our insurers and professional advisers, and some of those providers store or process information outside Australia, including in the United States. Our Privacy Policy explains how we handle your information and how to access or correct it or make a complaint.

Talk to us now
1300 730 499 service@megavar.com.au Hobart · Launceston · Adelaide · Newcastle · Gladstone
Doing it in-house?Hire partial discharge test sets

Explore Our other services

Power system studies including load flow, fault, protection coordination and harmonic analysis for HV networks and renewables, delivered by Megavar.

On-site resonant hipot testing of HV cables, GIS and power transformers to 500 kV, with partial discharge, on Megavar-owned sets. Call 1300 730 499.

HV reticulation and distribution design across Australia: overhead and underground networks, URD, powerline design and DNSP-ready drafting, 415V to 132kV.

Trusted by top enterprises for exceptional results

AusNet logo - Megavar clientABB logo - Megavar clientElectraNet logo - Megavar clientFluence logo - Megavar clientRJE Global logo - Megavar clientNYRStar logo - Megavar clientSchneider Electric logo - Megavar clientAcciona logo - Megavar clientRBD Electrical logo - Megavar clientVentia logo - Megavar clientGrange logo - Megavar clientAlcoa logo - Megavar clientZinfra logo - Megavar client Bison Energy Company logo - Megavar client Hydro Tasmania logo - Megavar client TasNetworks logo - Megavar clientVestas logo - Megavar client Goldwind logo - Megavar client Downer logo - Megavar client ENERVEN logo - Megavar client Genus logo - Megavar client

Testing guides

Related testing guides

Partial Discharge Testing Explained: Methods, Standards and What the Results Mean

Partial discharge testing finds insulation defects in HV cables, switchgear and transformers before they fail. This guide explains partial discharge detection, the difference between offline and…

VLF Cable Testing: A Field Guide to VLF Withstand, Tan Delta and Sheath Testing

VLF testing applies AC at 0.1 Hz to an MV or HV cable to prove its insulation, joints and terminations. This guide explains the withstand levels…

Hipot Testing: A Field Guide to HV Withstand Testing of Switchgear, GIS and Bushings

Hipot testing applies a voltage well above the operating voltage to insulation for a set time to prove it withstands it. This guide explains AC, resonant…

All testing guides

Testing services
Engineers Australia-wide
Request a quote