HV Cable Testing Services Australia
Verify the Integrity of Your High Voltage Cable Systems
Underground HV cables are critical and often inaccessible. A failure results in extended outages, expensive excavation, and significant consequential costs. Megavar provides comprehensive cable testing for XLPE, EPR, and PILC cables from 11 kV to 220 kV across Australia.
VLF Withstand Testing
VLF applies sinusoidal AC at 0.1 Hz above operating voltage to identify weakened insulation. The preferred acceptance method for XLPE cables per IEEE 400.2, avoiding space-charge damage caused by DC hipot.
VLF Partial Discharge Testing
Combined VLF withstand and PD measurement for the most comprehensive cable assessment. PD source location along the cable enables targeted investigation of defective joints, terminations, or sections.
DC Insulation and Hipot
Basic insulation assessment. DC hipot appropriate for PILC cables; VLF preferred for XLPE.
Sheath Integrity Testing
DC voltage between sheath and earth verifies outer protection. Sheath defects allow moisture ingress causing water treeing. Essential after installation, jointing, and civil works.
Tan Delta Testing
Cable insulation dissipation factor assessment for moisture, ageing, and degradation. Valuable for trending deterioration in aged XLPE and EPR cables.
Cable Fault Location
TDR (time-domain reflectometry) and thumper/acoustic methods locate faults to within metres, minimising excavation and repair time.
Frequently Asked Questions
HV Cable Testing Services Australia
What is VLF cable testing?
VLF (Very Low Frequency) testing applies a 0.1 Hz sinusoidal voltage to medium and high voltage cables to test insulation integrity. It is used for commissioning new cable installations, periodic maintenance testing, and fault diagnosis. VLF is the preferred method for testing XLPE and EPR cables.
What voltage levels can Megavar test cables to?
Our VLF test sets can apply up to 60 kV peak (testing cables rated up to 36 kV). For higher voltage cables, we use resonant test systems capable of testing cables rated up to 220 kV.
Can Megavar perform partial discharge testing on cables?
Yes. Megavar provides both online and offline partial discharge (PD) testing for HV cables, detecting localised insulation defects before they develop into full insulation failure.
How often should HV cables be tested?
New cables should be tested before energisation. For in-service cables, many asset owners adopt a 3 to 5 year testing cycle, with more frequent testing for critical circuits or cables showing signs of deterioration.
What is included in a cable testing report?
Yes. Megavar can mobilise to locate faults using VLF testing, time domain reflectometry (TDR), and acoustic/electromagnetic pinpointing techniques.
Does Megavar provide cable fault location services?
Every cable test report includes the test method and equipment used, applied voltage levels and duration, leakage current measurements, partial discharge results (if applicable), pass/fail assessment, and recommendations for remedial action.
Ready to commission your substation? Contact Megavar today on 1300 730 499 or visit our contact page to request a quote.
Explore Our other services
Trusted by top enterprises for exceptional results
Explore the latest insights
Megavar delivered HV testing and protection system commissioning for the Bluegrass BESS (Blue Grass) project in Queensland's Western Downs, working in partnership with
We’re incredibly excited to share a big milestone in Megavar’s story—we’ve officially opened our new Newcastle branch, located at 22 Gavey Street, Mayfield,
Megavar commissioned the Rosebery substation upgrade on Tasmania's remote West Coast, delivering HV testing and commissioning services for TasNetworks. The project involved commissioning