Testing and commissioning services

HV Cable Testing Services Australia 

Talk to an engineer: 1300 730 499 or service@megavar.com.au

Verify the Integrity of Your High Voltage Cable Systems


Underground HV cables are critical and often inaccessible. A failure results in extended outages, expensive excavation, and significant consequential costs. Megavar provides comprehensive cable testing for XLPE, EPR, and PILC cables from 11 kV to 220 kV across Australia.

ISO 9001, 14001 and 45001 certifiedLicensed in every Australian stateTeams in Hobart, Launceston, Adelaide and Newcastle
High voltage cable VLF withstand test on XLPE cable in Australia

VLF Withstand Testing

VLF applies sinusoidal AC at 0.1 Hz above operating voltage to identify weakened insulation. The preferred acceptance method for XLPE cables per IEEE 400.2, avoiding space-charge damage caused by DC hipot.

VLF Partial Discharge Testing

Combined VLF withstand and PD measurement for the most comprehensive cable assessment. PD source location along the cable enables targeted investigation of defective joints, terminations, or sections.

DC Insulation and Hipot

Basic insulation assessment. DC hipot appropriate for PILC cables; VLF preferred for XLPE.

Sheath Integrity Testing

DC voltage between sheath and earth verifies outer protection. Sheath defects allow moisture ingress causing water treeing. Essential after installation, jointing, and civil works.

Tan Delta Testing

Cable insulation dissipation factor assessment for moisture, ageing, and degradation. Valuable for trending deterioration in aged XLPE and EPR cables.

Cable Fault Location

TDR (time-domain reflectometry) and thumper/acoustic methods locate faults to within metres, minimising excavation and repair time.

Take it to your team

Capability statement

High-Voltage Resonant Hipot Testing

AC withstand testing to 500 kV on Megavar-owned resonant test sets, with partial discharge measurement.

Capability statement

High-Voltage Testing, Commissioning and Maintenance Services

Primary plant testing, protection and SCADA commissioning, substation maintenance and the design capability behind them.

Clients

What our clients say

Megavar are industry leaders in HV commissioning services, offering high quality commissioning services. They are experts in high voltage commissioning services, and their work is always on time, on budget and to the highest quality.

Shaun ColtonEngineering Manager Substations & BESS, Downer Group

Megavar has repeatedly demonstrated their ability to quickly mobilise their highly skilled technicians to meet project demands and effectively develop solutions in a highly proficient and professional manner.
Megavar have been a pleasure to deal with, and we look forward to continuing to work closely on future projects for years to come.

Matt LawlessDirector – High Voltage Contracting

FAQ

Frequently Asked Questions HV Cable Testing Services Australia

What is VLF cable testing?

VLF (Very Low Frequency) testing applies a 0.1 Hz sinusoidal voltage to medium and high voltage cables to test insulation integrity. It is used for commissioning new cable installations, periodic maintenance testing, and fault diagnosis. VLF is the preferred method for testing XLPE and EPR cables.

What voltage levels can Megavar test cables to?

Our VLF test sets can apply up to 60 kV peak (testing cables rated up to 36 kV). For higher voltage cables, we use resonant test systems capable of testing cables rated up to 220 kV.

Can Megavar perform partial discharge testing on cables?

Yes. Megavar provides both online and offline partial discharge (PD) testing for HV cables, detecting localised insulation defects before they develop into full insulation failure.

How often should HV cables be tested?

New cables should be tested before energisation. For in-service cables, many asset owners adopt a 3 to 5 year testing cycle, with more frequent testing for critical circuits or cables showing signs of deterioration.

What is included in a cable testing report?

Every cable test report includes the test method and equipment used, applied voltage levels and duration, leakage current measurements, partial discharge results (if applicable), pass/fail assessment, and recommendations for remedial action.

Does Megavar provide cable fault location services?

Yes. Megavar can mobilise to locate faults using VLF testing, time domain reflectometry (TDR), and acoustic/electromagnetic pinpointing techniques.

ISO Certified and Licensed in Every State

Megavar is certified to ISO 9001 (quality), ISO 14001 (environment) and ISO 45001 (safety), and holds electrical contractors licences in every Australian state.

Ready to commission your substation? Contact Megavar today on 1300 730 499 or visit our contact page to request a quote.

Contact Us

Request a quote

Tell us about the job

An engineer replies by the end of the next business day (Monday to Friday, 8:30 am to 5:00 pm). Scope still forming? Send what you have. Outage or urgent fault? Call to discuss the site, access window and mobilisation.

Scope status
Drag & Drop Files, Choose Files to Upload

* Required.

Megavar Pty Ltd (ABN 88 104 344 765) collects these details, and any file you attach, to prepare your quote, respond to your enquiry and keep a record of it, and to understand how enquiries reach us. If you do not provide them we may not be able to quote. We may share them with our IT, email and business system providers and, where relevant, our insurers and professional advisers, and some of those providers store or process information outside Australia, including in the United States. Our Privacy Policy explains how we handle your information and how to access or correct it or make a complaint.

Talk to us now
1300 730 499 service@megavar.com.au Hobart · Launceston · Adelaide · Newcastle · Gladstone
Doing it in-house?Hire cable test equipment

Explore Our other services

HV substation design and engineering across Australia: primary plant, secondary protection and SCADA. Megavar designs and delivers the full package.

High voltage testing and commissioning of substations, transformers, cables and switchgear by Megavar's own engineers, from five offices. Call 1300 730 499.

BESS maintenance and testing across Australia. Keep your battery energy storage system safe, available and performing with Megavar. Enquire today.

Trusted by top enterprises for exceptional results

AusNet logo - Megavar clientABB logo - Megavar clientElectraNet logo - Megavar clientFluence logo - Megavar clientRJE Global logo - Megavar clientNYRStar logo - Megavar clientSchneider Electric logo - Megavar clientAcciona logo - Megavar clientRBD Electrical logo - Megavar clientVentia logo - Megavar clientGrange logo - Megavar clientAlcoa logo - Megavar clientZinfra logo - Megavar client Bison Energy Company logo - Megavar client Hydro Tasmania logo - Megavar client TasNetworks logo - Megavar clientVestas logo - Megavar client Goldwind logo - Megavar client Downer logo - Megavar client ENERVEN logo - Megavar client Genus logo - Megavar client

Testing guides

Related testing guides

VLF Cable Testing: A Field Guide to VLF Withstand, Tan Delta and Sheath Testing

VLF testing applies AC at 0.1 Hz to an MV or HV cable to prove its insulation, joints and terminations. This guide explains the withstand levels…

Cable Fault Location: How Cable Faults Are Found With TDR, Arc Reflection and Pinpointing

Cable fault location finds the point where a power cable has failed so it can be repaired in one excavation. This guide explains fault diagnosis, TDR…

Partial Discharge Testing Explained: Methods, Standards and What the Results Mean

Partial discharge testing finds insulation defects in HV cables, switchgear and transformers before they fail. This guide explains partial discharge detection, the difference between offline and…

All testing guides

Testing services
Engineers Australia-wide
Request a quote