Home › Equipment Hire › Transformer Testing › CPC 100 vs TESTRANO 600

OMICRON CPC 100 vs TESTRANO 600: Transformer Test Set Comparison

The OMICRON CPC 100 and TESTRANO 600 both test power transformers on site, but they are built for different jobs. The CPC 100 is a multi-functional primary test system that also covers instrument transformers, earthing systems and primary injection. The TESTRANO 600 is a dedicated three-phase transformer test system. This page sets them side by side using OMICRON’s published specifications, so you can choose before you hire transformer test equipment.

Specifications side by side

Specification CPC 100 TESTRANO 600
Type Multi-functional primary test system Three-phase transformer test system
AC current 800 A (25 s), 400 A (8 min); 6 A and 3 A ranges 3 x 33 A; single-phase up to 50 A
DC current 400 A (2 min); 6 A range 3 x 33 A at 56 V; single-phase up to 100 A
AC voltage 2 kV, 1 kV, 500 V and 130 V ranges; 12 kV with the CP TD1 3-phase 0 V to 230 V line to neutral (400 V line to line)
Frequency 15 Hz to 400 Hz DC, 15 Hz to 599 Hz
Phases injected at once One Three
Weight 29 kg About 20 kg
Dimensions (W x H x D) 468 x 394 x 233 mm 580 x 386 x 229 mm
Supply 100 V to 240 V AC, 16 A 100 V to 240 V AC
Software Front panel and Primary Test Manager TouchControl and Primary Test Manager

Transformer tests each one covers

Test CPC 100 TESTRANO 600
Turns ratio per tap Yes Yes, three-phase
Winding resistance Yes Yes, three-phase
Dynamic resistance of on-load tap changers Yes Yes, with automatic tap changer control
Short-circuit impedance and leakage reactance Yes Yes
Frequency response of stray losses (FRSL) With the CP TD1 Yes
Excitation (magnetising) current With the CP TD1 Yes
Demagnetisation With the CP SB1 switch box Yes
Vector group With the CP SB1 switch box Yes
Power factor and dissipation factor With the CP TD1 With the CP TD12

Beyond power transformers, OMICRON lists the CPC 100 for CT and VT testing (ratio, burden, excitation), earthing system and line parameter measurements with the CP CU1, and primary injection. OMICRON does not list CT testing for the TESTRANO 600.

Points that usually decide it

  • Three-phase injection: the TESTRANO 600 tests all three phases in one connection, which shortens ratio, winding resistance and tap changer tests on a power transformer.
  • Range of jobs: the CPC 100 also covers CTs, VTs, earthing systems and high-current primary injection.
  • Current: the CPC 100 reaches 800 A AC and 400 A DC; the TESTRANO 600 tops out at 100 A DC single-phase.
  • Accessories: on the CPC 100, several transformer tests need the CP TD1 or the CP SB1.

Hire either set from Megavar

Both are in the Megavar hire fleet with published day rates, supplied calibrated with OMICRON’s manuals. See the CPC 100 hire page, the TESTRANO 600 hire page and the CP TD1, or call 1300 730 499. If you would rather have the testing done for you, see transformer testing.

Specifications are OMICRON’s published figures (CPC 100 brochure; TESTRANO 600 brochure, 2023; omicronenergy.com). The quote for your hire confirms the configuration supplied.

Hire the CPC 100Hire the TESTRANO 600

Enquire about Transformer Testing Equipment Hire

Check availability

Send your hire dates and delivery location and we will confirm availability and lead time by the end of the next business day.

Or call us directly on 1300 730 499

Dates and alternatives
Delivery or collection

* Required. This asks for availability and a price; it does not reserve the equipment. We reply by the end of the next business day. Hire within Australia only.

Megavar Pty Ltd (ABN 88 104 344 765) collects these details to check availability, quote your hire, arrange delivery or collection and keep a record of it, and to understand how enquiries reach us. If you do not provide them we may not be able to quote. We may share them with our IT, email and business system providers, with freight carriers for delivery and collection, and, where relevant, our insurers and professional advisers, and some of those providers store or process information outside Australia, including in the United States. Our Privacy Policy explains how we handle your information and how to access or correct it or make a complaint.