Omicron HVX10 for Hire 10 kV High-Voltage Source

From $420.00 (AUD ex GST per day. Weekly and monthly rates available.)

Tier 1: 1-7 days
$420.00 (AUD ex GST)
Tier 2: 8-14 days
$378.00 (AUD ex GST)
Tier 3: 15-28 days
$315.00 (AUD ex GST)
Tier 4: 29-90 days
$264.60 (AUD ex GST)
Description
The Omicron HVX10 is a compact 10 kV AC/DC high-voltage source that attaches to the CPX 200 multifunctional test set via Omicron’s Click-Snap-Lock mechanism. It adds capacitance, dissipation factor (tan delta or power factor) and insulation resistance testing to the CPX 200 platform, covering transformer bushings, grading capacitors, instrument transformers and other primary-asset insulation systems. Hire the HVX10 from Megavar as part of a CPX 200 package.
  • 10 kV AC and DC voltage source, switchable between AC and DC without rewiring, supporting both tan delta and insulation resistance with a single test setup
  • Frequency range 1 to 600 Hz, voltage and frequency sweep procedure detects moisture ingress, ageing and voltage-dependent insulation behaviour
  • Four current measurement inputs plus one voltage input, connecting up to four transformer bushings simultaneously without rewiring
  • Click-Snap-Lock attachment to CPX 200: fast, secure mechanical and electrical connection in seconds, with equally easy disconnection
  • Lightweight 14.8 kg construction: total CPX 200 plus HVX10 system stays under 30 kg, manageable as a backpack or trolley case
  • EtherCAT communication with CPX 200, providing fully integrated control, safety interlock, and CPXpert reporting
  • Red and green signal lights, EN 50191-compliant safety architecture inherited from the CPX 200 platform
  • Innovative lightweight high-voltage cable with optimised connector geometry, reducing test setup and pack-down time
  • Designed for transformer bushings, grading capacitors, instrument transformers, and Ratio V high-voltage transformer ratio testing

The HVX10 expands the CPX 200’s capability into insulation diagnostics and high-voltage ratio testing:

 

  • Power transformer bushing testing: capacitance and dissipation factor for condenser bushings (C1, C2, tap), with up to four bushings connected at once for sequential measurement without ladder climbs
  • Tan delta and power factor on grading capacitors of high-voltage circuit breakers, which detects early insulation degradation before flashover
  • Insulation resistance with Polarisation Index (PI) and Dielectric Absorption Ratio (DAR) on transformer windings, instrument transformers and switchgear
  • Voltage transformer Ratio V testing up to 10 kV, delivering higher accuracy than low-voltage ratio testing, particularly valuable on high-precision metering CTs and VTs
  • Frequency-domain insulation diagnostics, voltage and frequency sweep across 1 to 600 Hz reveals moisture, ageing, and voltage-dependent behaviour that single-frequency tan delta testing can miss
  • Routine condition assessment campaigns where the CPX 200 is already on site, adding high-voltage diagnostics without separate dedicated equipment
  • Omicron HVX10 system component
  • High-voltage output cable (Omicron lightweight design)
  • Four current measurement input leads
  • One voltage input lead
  • EtherCAT cable for CPX 200 connection
  • Booster IN supply cable
  • Measurement ground connection lead
  • Carry case (combinable with the CPX 200 carry case as a backpack)
  • Calibration certificate
  • User manual

Megavar’s commissioning engineers perform tan delta, capacitance, and insulation resistance testing on transformer bushings and instrument transformers as routine work on transmission and distribution projects. We understand which assets need which test sequence, what acceptance criteria apply, and where common pitfalls arise, particularly on aged condenser bushings and instrument transformers in service.

 

When you hire the HVX10 from Megavar, you receive it pre-configured to attach to a CPX 200 (or with a CPX 200 in the same package), with current calibration, full accessories and a wiring brief tailored to your scope. We can also advise on alternative configurations such as the Omicron CP TD1 (paired with the CPC 100) for projects where the CPX 200 platform is not yet specified. Hire from our offices in Hobart, Launceston, Adelaide and Newcastle, with delivery Australia-wide.

Hiring for 3, 6, or 12 months? Call for project rates: 1300 730 499

Enquire about Omicron HVX10 for Hire 10 kV High-Voltage Source Hire

Tell us about your project and we will get back to you within 24 hours with availability and a quote.

Or call us directly on 1300 730 499

Need help with your rental?

We’re available Mon – Fri 8am – 5pm

Australian engineering team
Calibrated and traceable to NMI
Pre-hire briefing on every order
Australia-wide delivery

Megavar engineers use this unit on commissioning projects across Australia. Hire it from a team that knows it inside out.

Calibration

All Megavar test equipment is maintained under a documented calibration programme. Instruments are calibrated either by external calibration laboratories or in-house against reference standards that are themselves laboratory-calibrated, with measurement traceable to Australian national measurement standards held by the National Measurement Institute. A current calibration certificate is available on request. If your project requires a specific calibration interval, test standard, or documentation for a client submission, tell us at enquiry on 1300 730 499 and we will confirm what applies before you commit.

Ask an Engineer

Have a setup or application question about this instrument? Talk directly to a Megavar commissioning engineer — no call centre, no guesswork.

1300 730 499

Frequently Asked Questions
Omicron HVX10 for Hire 10 kV High-Voltage Source

What is the Omicron HVX10 used for?

The Omicron HVX10 is a compact 10 kV AC/DC high-voltage source that adds capacitance, dissipation factor (tan delta or power factor), and insulation resistance testing to the Omicron CPX 200 multifunctional test set. It is used for diagnostic testing of transformer bushings, grading capacitors on high-voltage circuit breakers, instrument transformer insulation, and for high-voltage ratio testing of voltage transformers up to 10 kV. The HVX10 enables two measurement procedures (tan delta and insulation resistance) in a single test setup.

No. The HVX10 is a system component designed exclusively for the Omicron CPX 200. It draws its power supply from the CPX 200 via a dedicated Booster IN cable and communicates with the CPX 200 via EtherCAT, using the CPX 200’s display, controls, safety interlock and software. The HVX10 must be hired or used together with a CPX 200. Megavar offers combined CPX 200 plus HVX10 hire packages.

The HVX10 generates up to 10 kV AC and DC, switchable between AC and DC operation without rewiring. The frequency range is 1 to 600 Hz, which is significantly wider than legacy single-frequency tan delta accessories. This wide frequency range enables a voltage and frequency sweep test procedure that detects moisture ingress, premature ageing and voltage-dependent insulation behaviour that fixed-frequency testing can miss.

Yes. Testing transformer bushings is one of the HVX10’s primary use cases. The HVX10 has four current measurement inputs, which allow up to four bushings to be connected to the test setup simultaneously. Each bushing is then measured sequentially without rewiring, sharply reducing ladder climbs and total test time. The HVX10 measures capacitance and dissipation factor on the main insulation (C1) and tap insulation (C2 or tap-to-ground) of condenser bushings.

Both accessories enable tan delta, capacitance, and insulation diagnostics, but they belong to different platforms. The CP TD1 attaches to the Omicron CPC 100 (the previous-generation primary test platform) and is the established choice for tan delta on transformers, bushings and surge arresters paired with the CPC 100. The HVX10 attaches to the new CPX 200 (released October 2025), offers a wider frequency range (1 to 600 Hz), provides four simultaneous current inputs for bushing testing, and integrates with the CPXpert software and CORTEX Grid cloud platform. Both are available for hire from Megavar.

Yes. With its integrated 10 kV DC source, the HVX10 performs insulation resistance testing with both Polarisation Index (PI) and Dielectric Absorption Ratio (DAR) calculations. Unlike traditional megohmmeters, the HVX10 can perform insulation resistance and tan delta in a single test setup; once the asset is connected, the operator can run both measurements in sequence without re-cabling, which is a substantial time saving on multi-bushing transformer or instrument transformer testing.

The HVX10 weighs 14.8 kg. It attaches to the CPX 200 using Omicron’s Click-Snap-Lock quick-release mechanism, which engages the mechanical, electrical, and EtherCAT communications connections in a single action. The two units can be connected for transport and use as a single integrated system, then disconnected just as easily for separate carry. The total CPX 200 plus HVX10 system stays under 30 kg, supporting backpack or trolley-case transport.

The HVX10 is supplied as part of a combined CPX 200 hire package, since it is not a standalone test set. Megavar offers several configurations: CPX 200 base unit only, CPX 200 with High Current Module (1000 A AC/DC), CPX 200 with HVX10 (10 kV AC/DC), or CPX 200 with both High Current Module and HVX10. Specify the configuration required when enquiring on 1300 730 499 or rentals@megavar.com.au, and we will quote the appropriate package.

Tan delta and power factor testing of transformer bushings is typically referenced to IEEE C57.19.01 and IEC 60137 acceptance criteria. Tan delta on instrument transformers is referenced to IEC 61869 and the asset owner’s relevant maintenance specification. Insulation resistance testing follows IEEE 43 for rotating machines or asset-specific manufacturer guidance. Megavar’s engineers can advise on the specific acceptance values that apply to your equipment and project, and CPXpert provides automated assessment against industry-standard limits.

Yes. Megavar provides full diagnostic testing services using the CPX 200 with HVX10, the CPC 100 with CP TD1, the Omicron MPD 600 partial discharge system, and the Omicron Dirana dielectric response analyser, depending on what your asset condition assessment requires. If your project needs a complete diagnostic service rather than equipment hire alone, contact us with your scope and we will quote a turnkey service delivered by experienced commissioning engineers.

A Tailored Hire Experience That Works for You

At Megavar, our dedicated test equipment hire division provides high-quality electrical testing instruments for both short and long-term use. Backed by deep industry expertise, our team ensures you receive the right tools with the right advice, every time. From fast dispatch to full technical support, our hiring process is streamlined to get you up and running quickly and confidently.
 
  • Rapid delivery and collection
  • Door-to-door freight for minimal downtime
  • Fast, simple bookings
  • Place an order and we’ll handle the rest
  • Rent, try or buy
  • Test the equipment before committing to purchase
  • Expert support
  • Technical help is just a call away when you need it.

Our 3-step easy process

Hiring Made Easy in 3 Simple Steps

Step 1: Request a Quote

Submit your rental request online, and our team will respond promptly with availability, pricing, and expert advice.

Step 2: Organise Your Rental

Once confirmed, we’ll quickly process your booking and dispatch the equipment. Delivery and collection can be arranged to suit your schedule.

Step 3: Use with Confidence

Get to work with reliable, industry-grade test equipment. Our technical team is available to support you every step of the way.

Explore Our Services

Circuit breaker testing across Australia: timing analysis, contact and dynamic resistance, insulation and SF6/vacuum integrity testing on HV and MV breakers, fully reported.

HV substation design and engineering across Australia: primary plant, secondary protection and SCADA. Megavar designs and delivers the full package.

Arc flash studies and hazard analysis across Australia: incident energy and arc flash boundary calculation to IEEE 1584, PPE and labelling, and mitigation design.

Trusted by top enterprises for exceptional results

AusNet logo - Megavar client
ABB logo - Megavar client
ElectraNet logo - Megavar client
Fluence logo - Megavar client
RJE Global logo - Megavar client
NYRStar logo - Megavar client
Schneider Electric logo - Megavar client
Acciona logo - Megavar client
RBD Electrical logo - Megavar client
Ventia logo - Megavar client
Grange logo - Megavar client
Alcoa logo - Megavar client
Zinfra logo - Megavar client
Bison Energy Company logo - Megavar client
Hydro Tasmania logo - Megavar client
TasNetworks logo - Megavar client
Vestas logo - Megavar client
Goldwind logo - Megavar client
Downer logo - Megavar client
ENERVEN logo - Megavar client
Genus logo - Megavar client

Explore the latest insights